Description
Hi,
In the project's wiki it's mentioned that, though not tested, it probably works also in F and S-series.
However, the pinout for the invertor connector seems to be different, as can be read in the User Manuals of the different series (https://www.fox-ess.com/downloads/#1608629474343-a4d4beb2-71e3; page 16 of F Series User Manual, for instance).
In F and S-series pin 7 is “NC” (not connected), it doesn’t supply the +12V as in T. And pins 1 and 2 are used for CT (the Current Transformer sensor of the AC line); so we cannot access RS485 through these pins.
Pins 3 and 4 are, in all three series, assigned to Meter 485. I wonder if their usage is restricted to the connection of a limiting meter, as explained in the manuals, or they are also available for plain RS485 connection. That would allow me to use this setup, though wiring (and powering of circuits) should be different.
Thanks and regards